Installation Instructionsvariable, the probe should be close to the work area.Some experimenting with probe location is oftenneeded to find its optimu
Operating InstructionsStart-Up Before line voltage is applied, double check all itemsconnected to controller: The correct type thermocouple(see sectio
Operating InstructionsTuningHeat GainHeat Gain(HG) SettingRate (RT)Setting(includes reset)relays directly connected to small heaters, 0-5 sec., butnot
Operating Instructions(with some overshoot) reduce rate time 10-20%. For more anticipation (givingundershoot) increase rate slightly. Experiment with
TroubleShootingUnit RepairsFront dark - no instrument power, blown fuse or burnedout transformer.Process display shows CCCC - Open thermocouple.Short
Athena 6000/6200Microprocessor-based Temperature ControllerDesigned for the userAthena’s unique new 6000microprocessor-based controllerwas developed t
SpecificationsInputs:Line VoltageSensorPower consumption:Ranges available:Accuracy:Temperature stability:Cold end tracking:Operating ambient forrated
Front Panel AdjustmentsTouch KeyIndex: Allows the following adjustments to be selected.1) set point temperature
Output ModulesModule Type F:Module Type T:Module Type S:times less than ten seconds will drastically shortenrelay life and in no case should the cycle